Untitled Document
■ Kinds
Poles
Classification
|
2 Poles
|
4Poles
|
Rated voltage
|
Mode
|
Rated voltage
|
Mode
|
Basic type
(YM2-A,YM4-A)
|
AC6,12,24,50,
100/110,110/120
200/120,220/240
|
YM2-A
|
AC6,12,24,50,
100/110,110/120
200/120,220/240
|
YM4-A
|
DC6,12,24,48,
100/110
|
DC6,12,24,48,
100/110
|
LED operating display
lamps
(YM2-L,YM4-L)
|
AC6,12,24,50,
100/110,110/120
200/120,220/240
|
YM2-L
|
AC6,12,24,50,
100/110,110/120
200/120,220/240
|
YM4-L
|
DC6,12,24,48,
100/110
|
DC6,12,24,48,
100/110
|
Interior diodes
(YM2-LD,YM4-LD)
|
DC6,12,24,48,
100/110
|
YM2-D
|
DC6,12,24,48,
100/110
|
YM4-D
|
LED operating display
lamps and interior diodes
(YM2-LD,YM4-LD)
|
DC6,12,24,48,
100/110
|
YM2-LD
|
DC6,12,24,48,
100/110
|
YM4-LD
|
LED operating display
lamps and interior C-R
(YM2-LCD,YM4-LCR)
|
AC6,12,24,50,
100/110,110/120
200/120,220/240
|
YM2-LCR
|
AC6,12,24,50,
100/110,110/120
200/120,220/240
|
YM4-LCR
|
■ Characteristics
Kinds
Items
|
Basic pttem
|
LED operating display lamps
and interior diodes
|
Contact resistance
|
Max. 50mΩ(by voltage drop DC 6V 1A)
|
Operating time(at nominal voltage)
|
Max.20ms
|
Release time(at nominal voltage)
|
Max.20ms
|
Max.
switching frequency
|
Mechanical
|
18,000/per hour
|
Electical
|
1,800/per hour (rated current)
|
Insulation resistance
|
Min. 100MΩ (DC 500V Megger)
|
Dielectric strength
|
AC 2000V(50/60Hz) for 1 minute(1000V between
same pole contacts)
|
Vibration
resistance
|
Functional
|
10 to 50Hz at double amplitude of 1.0mm
|
Destructive
|
10 to 50Hz at double amplitude of 1.0mm
|
Shock
reistance
|
Functional
|
1,000 ㎨ (about 100G)
|
Destructive
|
200 ㎨ (about 20G)
|
Life
expctancy
|
Mechanical
|
Min.AC : 50,000,000 operations, 4 poles
: 200,000 operations
(switching frequency : 18,000 times per hour)
|
Electical
|
Min. 2 poles : 500,000 operations, 4 poles
:200,000 operations(switching frequency : 18,000 times rated load)
|
Rating
Characteristic DATA(YM2
Type)
Perfomance Characteristic
curve(YM4 Type)
External sizes(YM2)/ Terminal
arrangement plan & inter connection diagram / Socket
External sizes(YM4) / Terminal
arrangement plan & inter connection diagram / Socket
|